RELAY IMPLEMENTATIONS OF
FLASHING YELLOW ARROWS

Making older signal controllers work with Flashing Yellow Arrows:

While many older signal controllers can't be programmed to directly work with Flashing Yellow Arrows (FYA), they can be fooled into using them with simple relay logic. As far as the controller is concerned, it is running an exclusively protected left turn sequence. And although older conflict monitors can't deal with FYA, they can still be used to prevent the most dangerous combinations.

Note that the first three implementations do not use overlap phases. This allows this method to be used where overlap phases are all in use, or where they do not exist. But be careful that the overlap phases used for right turns do not cause Second Yellow Trap.

Note that more than one of these circuits can be used where more Flashing Yellow Arrows are needed. The FYA faces should usually be installed in pairs. Also note that the relays can be solid state relays (SSR) properly matched to the voltages and currents being controlled.

The relays placed after the load switches must be able to handle the currents of the lamps, with plenty of capacity to spare. The relays before the load switches can be small signal relays.

WARNING: This must be implemented by a properly trained engineer who knows the dangers of yellow trap. Because the wrong application of these ideas can endanger lives, this must not be done by politicians or electricians who do not fully understand the dangers. Specifically, the flashing yellow arrow face MUST be tied to the oncoming straight ahead phase, NOT the straight ahead phase for the same approach the flashing yellow arrow face is on.

Permissive Left for Yellow Trap Problem with no Left Turn Phase

No Relays

Permissive left turn

This is used where the flashing yellow arrow is needed to prevent yellow trap from an opposing left turn phase or a pre-emption.


Basic
Monitor
Programmable
Monitor
LampCon-
flict
Dark
Face
Burn
Out
Con-
flict
Dark
Face
Burn
Out
Φ2 RYesYesNoYesYesNo*
Φ2 YYesYesNoYesYesNo*
Φ2 GYesYesNoYesYesNo*
D2 RYesYesNoYesYesNo*
D2 YYesYesNoYesYesNo*
D2 FYYesYesNoYesYesNo*

* The second load switch (D2) shown can be used to improve conflict monitoring, making these entries Yes.

The phase D2 is the left turn that turns across the phase Φ2. This circuit derives it from Φ2. It does not exist in the controller.


Sequence
Signal 1  2  3   4  5  6 
Φ2RGYRR-
O2RFYYRR-
OtherRRRROK-

SSR = Solid State Relay.

Protected/Permissive Left for Yellow Trap Problem with No Overlap Phase

Relays After the Load Switches

Basic FYA P/P

This is used where the flashing yellow arrow is needed to prevent yellow trap from an opposing left turn phase or a pre-emption.


Basic
Monitor
Programmable
Monitor
LampCon-
flict
Dark
Face
Burn
Out
Con-
flict
Dark
Face
Burn
Out
Φ2 RYesYesYesYesYesYes
Φ2 YYesYesYesYesYesYes
Φ2 GYesYesYesYesYesYes
Φ1 RYesNoYesYesYesYes
Φ1 YYesNoYesYesYesYes
Φ1 FYYesNoNoYesYesYes
Φ1 GYesNoYesYesYesYes

The phase Φ1 is the left turn that turns across the phase Φ2.

The dummy loads will not affect the conflict monitor's ability to detect lamp burnout if there are red clearance periods on all affected phases, because:

  • There will then be sufficient periods of time when the real lamp is connected and the load switch is on, and also when it is off.
  • There will also be sufficient periods when any extra lamp is disconnected and the load switch is on, and also when it is off.

The dummy loads prevent false tripping when no lamp is connected.

Dummy loads are not needed with the programmable monitors.


Sequence
Lead
Left
 1  2  3  4   5   6  7  8  9 
Φ1RGYRFYYRR-
Φ2RRRRGYRR-
OtherRRRRRRROK-
Lag
Left
 1  2  3  4   5   6  7  8  9 
Φ1RFYYRGYRR-
Φ2RGYRRRRR-
OtherRRRRRRROK-

Protects one left-turn and opposing straight-ahead pair from yellow trap.

Protected/Permissive Left for Yellow Trap Problem with No Overlap Phase

Relays Before the Load Switches

Basic FYA P/P

This is used where the flashing yellow arrow is needed to prevent yellow trap from an opposing left turn phase or a pre-emption.


Basic
Monitor
Programmable
Monitor
LampCon-
flict
Dark
Face
Burn
Out
Con-
flict
Dark
Face
Burn
Out
Φ2 R---YesYesYes
Φ2 Y---YesYesYes
Φ2 G---YesYesYes
Φ1 R---YesYesYes
Φ1 Y---YesYesYes
Φ1 FY---YesYesYes
Φ1 G---YesYesYes

The phase Φ1 is the left turn that turns across the phase Φ2.


Sequence
Lead
Left
 1  2  3  4   5   6  7  8  9 
Φ1RGYRFYYRR-
Φ2RRRRGYRR-
OtherRRRRRRROK-
Lag
Left
 1  2  3  4   5   6  7  8  9 
Φ1RFYYRGYRR-
Φ2RGYRRRRR-
OtherRRRRRRROK-

Protects one left-turn and opposing straight-ahead pair from yellow trap.

Protected/Permissive Left for Yellow Trap Problem with One Overlap Phase

Relays After the Load Switches

Advanced FYA P/P

This is used where the flashing yellow arrow is needed to prevent yellow trap from an opposing left turn phase or a pre-emption.

Uses one overlap phase to control both left turn signals. This version does not have to stop the flashing yellow arrow movement before starting the green arrow.


Basic
Monitor
Programmable
Monitor
LampCon-
flict
Dark
Face
Burn
Out
Con-
flict
Dark
Face
Burn
Out
Φ1,5 RYesNoNoYesYesYes
Φ1,5 YYesNoNoYesYesYes
Φ1,5 FYNoNoNoYesYesYes
Φ1,5 GYesNoNoYesYesYes

The phase Φ1 is the left turn that turns across the phase Φ2.
The phase Φ5 is the left turn that turns across the phase Φ6.
Overlap Phase OA is green whenever Φ1, Φ2, Φ5, or Φ6 is green.

Lamp and dark face checking is not possible with the basic monitor.


Sequence
Lead
Left
 1  2  3  4   5   6  7  8  9  10  11
Φ1RGGGYRFYYR R-
Φ2RRRRRRGYR R-
Φ5RGYRFYFYFYYR R-
Φ6RRRRGGGYR R-
OARGGGGGGYR R-
OtherRRRRRRRRR OK-
Lag
Left
 1  2  3  4   5   6  7  8  9  10  11
Φ1RFYFYFYFYFYGYR R-
Φ2RGGGYRRRR R-
Φ5RFYFYFYGGGYR R-
Φ6RGYRRRRRR R-
OARGGGGGGYR R-
OtherRRRRRRRRR OK-
Lead-
Lag
 1  2  3  4   5   6  7  8  9  10  11
Φ1RGYRFYFYFYYR R-
Φ2RRRRGGGYR R-
Φ5RFYFYFYFYFYGYR R-
Φ6RGGGYRRRR R-
OARGGGGGGYR R-
OtherRRRRRRRRR OK-

Protects two left-turn and straight-ahead pairs on the same street from yellow trap.

Protected/Permissive Left for Yellow Trap Problem with One Overlap Phase

Relays Before the Load Switches

Advanced FYA P/P

This is used where the flashing yellow arrow is needed to prevent yellow trap from an opposing left turn phase or a pre-emption.

Uses one overlap phase to control both left turn signals. This version does not have to stop the flashing yellow arrow movement before starting the green arrow.


Basic
Monitor
Programmable
Monitor
LampCon-
flict
Dark
Face
Burn
Out
Con-
flict
Dark
Face
Burn
Out
Φ1,5 R---YesYesYes
Φ1,5 Y--YesYesYes
Φ1,5 FY---YesYesYes
Φ1,5 G---YesYesYes

The phase Φ1 is the left turn that turns across the phase Φ2.
The phase Φ5 is the left turn that turns across the phase Φ6.
Overlap Phase OA is green whenever Φ1, Φ2, Φ5, or Φ6 is green.


Sequence
Lead
Left
 1  2  3  4   5   6  7  8  9  10  11
Φ1RGGGYRFYYR R-
Φ2RRRRRRGYR R-
Φ5RGYRFYFYFYYR R-
Φ6RRRRGGGYR R-
OARGGGGGGYR R-
OtherRRRRRRRRR OK-
Lag
Left
 1  2  3  4   5   6  7  8  9  10  11
Φ1RFYFYFYFYFYGYR R-
Φ2RGGGYRRRR R-
Φ5RFYFYFYGGGYR R-
Φ6RGYRRRRRR R-
OARGGGGGGYR R-
OtherRRRRRRRRR OK-
Lead-
Lag
 1  2  3  4   5   6  7  8  9  10  11
Φ1RGYRFYFYFYYR R-
Φ2RRRRGGGYR R-
Φ5RFYFYFYFYFYGYR R-
Φ6RGGGYRRRR R-
OARGGGGGGYR R-
OtherRRRRRRRRR OK-

Protects two left-turn and straight-ahead pairs on the same street from yellow trap.

Note that the last four systems have switches for changing the mode to exclusively protected, protected/permissive, or exclusively permissive. These switches must not be moved unless all signals for the street they control are red.


Using these circuits with a standard NEMA Dual Ring configuration:

ConfigurationModel PhaseAdditional Phases
Exclusively Permissive FYAΦ2 (D2 is Φ1 turn)Φ6 & D2 Φ4 & D4Φ8 & D8
Prot/Perm FYA No OverlapΦ1 & Φ2Φ5 & Φ6 Φ3 & Φ4Φ7 & Φ8
Overlap phaseOA if Φ1, Φ2, Φ5 or Φ6 OB if Φ3, Φ4, Φ7, or Φ8
Prot/Perm FYA With OverlapΦ1, Φ5, & OAΦ3, Φ7 & OB

Note that the normal pedestrian phases can be used with Φ2, Φ6, Φ4, or Φ8

Right turn arrows should not be used with overlap phases, or Second Yellow Trap will occur.

STANDARD NEMA
PHASE ASSIGNMENT
 arrarr   
 476 arr
arr5 1 arr
arr238 
  arr arr 
Phase 2 is the main road,
northbound or eastbound.

Proof These Systems Are Safe

When Properly Installed by Trained Engineers

  1. System Without Left Turn Phase
  2. Systems With Left Turn Arrows, but No Overlaps
  3. Systems With Left Turn Arrows and an Overlap
  4. Failure of the relay to energize or release will cause the system to default to exclusively permissive or exclusively protected. Other failures in the relay will activate the conflict monitor.